Got Side Settings - Mitsubishi Electric GOT1000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

8.4 GOT Side Settings

8.4.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: JTEKT
• Controller Type: JTEKT TOYOPUC-PC
• I/F: Interface to be used
• Driver: JTEKT TOYOPUC-PC
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
8.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
8 - 14
8. CONNECTION TO JTEKT PLC
8.4 GOT Side Settings
Click!
[Controller Setting] from the
8.4.2
Make the settings according to the usage environment.
3.
4.
Item
Transmission
Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
Host Address
Delay Time
Format
Communication detail settings
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is
performed during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station
No. of the GOT to which the PLC is
connected) in the connected
network.
(Default: 00)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0)
Select the communication format.
(Default: 1)
format 1: PC3J extended function
incompliant
format 2: PC3J extended function
compliant
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
00 to 37
(Octal)
0 to 300ms
1/2

Advertisement