Mitsubishi Electric GOT1000 Series Connection Manual page 379

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

*1
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Ethernet setting
(2) GT15, GT12
Item
Description
Set the network No. of the GOT.
GOT NET No.
(Default: 1)
Set the station No. of the GOT.
GOT PLC No.
(Default: 1)
Set the IP address of the GOT.
GOT IP Address
(Default: 192.168.3.18)
Set the subnet mask for the sub
network. (Only for connection via
Subnet Mask
router) If the sub network is not
used, the default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
Default Gateway
connected. (Only for connection via
router)
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for Ethernet
Download Port
download.
No.
(Default: 5014)
Set the GOT port No. for the
GOT
connection with the Ethernet
Communication
module.
*1
Port No.
(Default: 5022)
Item
Retry
Startup Time
Timeout Time
Delay Time
Ethernet setting
Item
Host
N/W No.
PLC No.
Type
Range
1 to 239
IP Address
1 to 254
Port No.
0.0.0.0 to
255.255.255.255
Communication
0.0.0.0 to
255.255.255.255
0.0.0.0 to
POINT
POINT
POINT
255.255.255.255
(1) Communication interface setting by the Utility
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
(2) Precedence in communication settings
5012, 5013 and
49153)
12. CONNECTION TO TOSHIBA PLC
Description
Set the number of retries to be
performed when a communication
timeout occurs.When receiving no
response after retries, the
communication times out. (Default:
3times)
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
PLC. (Default: 0ms)
Description
The host is displayed. (The host is
indicated with an asterisk (*).)
Set the network No. of the
connected Ethernet module.
(Default: blank)
Set the station No. of the
*1
connected Ethernet module.
(Default: blank)
TOSHIBA (fixed)
Set the IP address of the
connected Ethernet module.
(Default: blank)
Set the port No. of the connected
Ethernet module.
(Default: 1024)
UDP (fixed)
*1
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
 Communication detail settings
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
User's Manual of GOT used.
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
12.3 Ethernet Connection
9
Range
0 to 5times
3 to 255sec
10
3 to 90sec
0 to 10000
( 10ms)
11
12
Set value
-
13
1 to 127
1 to 254
TOSHIBA (fixed)
PLC side IP
address
14
256 to 65534
UDP (fixed)
15
12 - 11