PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Alarm
Name
Configuring
board ...
Failed to
configure
board
Board
quantity
inconsistenc
y
Loading
board ...
Failed to
load board
Abnormal
board power
supply
Main input
open phase
Issue 01 (2019-02-25)
Alarm
Impact
Severity
Warning
The MDU is
configuring the
power
distribution
detection board.
Failed to
Critical
configure the
power
distribution
detection board.
Critical
The actual
number of power
distribution
detection boards
is different from
the configured
number.
Warning
The application is
being loaded to
the power
distribution
detection board.
Failed to load the
Critical
application to the
power
distribution
detection board.
Major
The voltage of a
power input to
the detection
board is less than
9.5 V.
Critical
A phase of the
input power has
no voltage or has
a voltage lower
than the threshold
(0–60 V).
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
Possible
Solutions
Cause
The MDU is
N/A
configuring
the power
distribution
detection
board.
The MDU
Use the latest upgrade
version does
package to activate the
not match the
board.
power
distribution
monitoring
board.
The
Check whether the
monitoring
run indicator of the
board is
monitoring board is
faulty.
steady on. If no,
replace the
A cable
monitoring board
has
by referring to
become
Replacing the
loose.
Monitoring
Check whether the
CAN cable is
securely connected.
N/A
Load again. If the fault
persists, contact
Huawei technical
support.
Load again. If the fault
N/A
persists, contact
Huawei technical
support.
N/A
Replace the
monitoring board by
referring to
Replacing the
Monitoring
The input
Check the input power.
power supply
is faulty.
8.5.5
Board.
8.5.5
Board.
128