5.3.3 Installing the PDC on an ESD Floor

Context
A support is required when the PDC is installed on an ESD floor. The support height depends
on the height between the ground and the ESD floor.
Procedure
Step 1 Lower the leveling feet of the PDC using an adjustable wrench until all castors are off the
ground.
Step 2 Lift the PDC onto the support and align the mounting holes on the PDC with those on the
support.
Step 3 Level the PDC by adjusting the leveling feet, as shown by (1) and (3) in
Step 4 Insert four M12 bolts into the mounting holes on the PDC and support, and tighten the bolts,
as shown by (2) in
Figure 5-9 Leveling and tightening bolts
(1) Leveling foot
Step 5 (Optional) Combine cabinets.
1.
2.
Issue 01 (2019-02-25)
Figure
5-9.
In the cabinet combination scenario, the bolts need to be pretightened.
Remove the front and rear doors of the PDC and level the PDC, as shown by (1) in
Figure
5-10.
Remove the cabinet connecting plates from the rack, as shown by (2) in
Copyright © Huawei Technologies Co., Ltd.
(2) Fixing bolt
5 Installation Guide
Figure
5-9.
(3) Level
Figure
5-10.