PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Figure 5-33 Connecting the monitoring cable
(1) Monitoring cable outlet
In the micro-module scenario, the monitoring cable is connected to the COM port of the
northbound ECC800.
Step 9 Use diagonal pliers to cut cable inlet and outlet holes on rodent-proof meshes based on the
number and specifications of cables to be routed.
Figure 5-34 Cutting holes in the rodent-proof meshes
Step 10 Reinstall the rodent-proof meshes.
Step 11 (Optional) Seal cable inlet and outlet holes on the PDC using firestop putty.
Step 12 Reinstall the transparent covers of the input copper bar and N bar.
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
5 Installation Guide
60