PDU8000 Modular Precision Power Distribution Cabinet

User Manual (1100 mm Deep)
The value ranges from 50 to 800.
The value ranges from 50 to 800.
The value ranges from 150 to 500.
The value ranges from 2 to 63.
The value ranges from 2 to 63.
The value ranges from 2 to 63.
The value can be Enable or Disable.

7.4.3.3 Branch Param.

On the Settings screen, tap Branch Param. to set circuit breaker parameters in Set CI Ratio
and Set Rated Current.
Issue 01 (2019-02-25)
Main input 1 CT ratio
Main input 2 CT ratio
Br. cur. shock threshold (%)
x harmonic frequency
y harmonic frequency
z harmonic frequency
Harmonic alarm
Harmonic alarm detection enable
Allows you to enable or disable alarms. By default, the Main input
overfrequency, Main input underfrequency, and Main input breaker off alarms
are set to Enable.
the Transformer over temperature, Transformer high temperature, and Branch
abnormal alarms are set to Disable.
The Branch abnormal and Br. circuit breaker off alarms have no default settings,
and can be customized based on the branch numbers.
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
98