The value ranges from 50 to 800.
The value ranges from 50 to 800.
The value ranges from 150 to 500.
The value ranges from 2 to 63.
The value ranges from 2 to 63.
The value ranges from 2 to 63.
The value can be Enable or Disable.

7.4.3.3 Branch Param.

On the Settings screen, tap Branch Param. to set circuit breaker parameters in Set CI Ratio
and Set Rated Current.
Issue 02 (2016-11-10)
Main input 1 CT ratio
Main input 2 CT ratio
Br. cur. shock threshold (%)
x harmonic frequency
y harmonic frequency
z harmonic frequency
Harmonic alarm
Alarm settings
Enable or disable the Main input overfrequency, Main input underfrequency,
and Main input breaker off alarms, which are enabled by default.
Enable or disable the Transformer over temperature, Transformer high
temperature, and Branch abnormal alarms, which are disabled by default.
Enable or disable the Branch abnormal and Br. circuit breaker off alarms for all
branches, or customize the settings based on branch numbers.
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
93