PDU8000 Modular Precision Power Distribution Cabinet
User Manual
No.
2
3
4
5
6
7
8
Figure 5-10 Cable ties without sharp burs
Figure 5-11 Cable ties in the same direction
Issue 02 (2016-11-10)
Cable Binding Rule
Both ends of a cable are labeled. Labels are clean and correct, and provide
concise and understandable description.
Cable ties are neatly cut without sharp burs, evenly distributed, bound to a
proper strength, and fastened towards the same direction if possible, as
shown in
Figure 5-10
Each bundle contains no more than 15 cables, and cables are neatly bound.
Extra cables are coiled neatly and easy to find.
Cables on the surface of a large cable bundle are neatly organized without
unnecessary crossover.
Cables are arranged in distinct layers and crossovers are avoided if
possible when cables in different colors are bound together, as shown in
Figure
5-12. Cables are arranged by thickness when arrangement by
thickness conflicts with arrangement by color.
Cables are reliably bound along the route, and the binding interval meets
the requirements in
Table
Copyright © Huawei Technologies Co., Ltd.
and
Figure
5-11.
5-4.
5 Installation Guide