PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Set an Ethernet gateway. The value ranges from 0.0.0.0 to 255.255.255.255. The default value
is 192.168.0.1.
Set the serial port communications rate. The value options include 4800, 9600, and 19200.
The default value is 9600.
Set the serial port communications address. The value ranges from 0 to 254. The default value
is 1.
SNMP Version can be set to ALL, SNMPv1&v2c, or SNMPv3. SNMP Port can be set to a
value in the range from 1 to 65535. The default value is 161.

7.4.3.2 System Param.

On the Settings screen, tap System Param. to enter the screen.
Figure 7-48 Settings
Issue 01 (2019-02-25)
Serial port baud rate
Serial port address
SNMP
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
94