[Quick Menu]
allows quick access to different Quick Menus such as:
-
Quick Start
-
Parameter Data Check
-
Trending
Use
[Quick Start]
for programming the parameters belonging to the Quick Menu. It is possible to switch directly between Quick Menu mode and Main Menu mode.
[Main Menu]
is used for programming all parameters.
It is possible to switch directly between Main Menu mode and Quick Menu mode.
Parameter shortcut can be carried out by pressing down the
[Alarm Log]
displays an Alarm list of the five latest alarms (numbered A1-A5). To obtain additional details about an alarm, use the arrow keys to maneuver to the
alarm number and press [OK]. You will now receive information about the condition of your frequency converter right before entering the alarm mode.
[Back]
takes you to the previous step or layer in the navigation structure.
[Cancel]
annuls your last change or command as long as the display has not been changed.
[Info]
supplies information about a command, parameter, or function in any
display window. [Info] provides detailed information whenever help is needed.
Exit info mode by pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between the different choices available in
the cursor.
[OK]
is used for choosing a parameter marked by the cursor and for enabling the change of a parameter.
Local Control Key
for local control are found at the bottom of the control
panel.
[Hand ]
enables control of the frequency converter via the Keypad. [Hand ] also starts the motor, and it is now possible to enter the motor speed data by means
of the arrow keys. The key can be selected as Enable [1] or Disable [0] via par. K-40 [Hand] Button on Keypad
External stop signals activated by means of control signals or a serial bus will override a "start" command via the Keypad.
The following control signals will still be active when [Hand ] is activated:
[Hand] - [Off] - [Auto]
Reset
Coasting stop inverse
Reversing
Set-up select bit 0- Set-up select bit 1
Stop command from serial communication
Quick stop
DC brake
[Main Menu]
key for 3 seconds. The parameter shortcut allows direct access to any parameter.
[Quick
Menu],
AF-650 GP Programming Guide
[Main Menu]
and
[Alarm
Log]. Use the keys to move
2