GE AF-650 GP Programming Manual page 45

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

NB!
Switching frequencies higher than 5.0 kHz lead to automatic derating of the maximum output of the frequency converter.
F-38 Overmodulation
Option:
[0]
Off
3
[1] *
On
3.3.5 F-4# Fundamental 4
Parameters to configure drive torque and current limits.
F-40 Torque Limiter (Driving)
Range:
160.0 %*
[0.0 - 1000.0 %]
Changing par. F-40 Torque Limiter (Driving) when par. H-40 Configuration Mode is set to Speed open loop [0], par. H-66 Min. Current at Low
Speed is automatically readjusted.
F-41 Torque Limiter (Braking)
Range:
100.0 %*
[0.0 - 1000.0 %]
F-43 Current Limit
Range:
160.0 %*
[1.0 - 1000.0 %]
3.3.6 F-5# Extended References
Parameters to configure drive min/max reference and reference function.
F-50 Reference Range
Option:
[0]
Min - Max
[1] *
-Max - +Max
44
Function:
Select On [1] to connect the overmodulation function for the output voltage, to obtain an output voltage
up to 15% greater than the mains voltage.
Select Off [0] for no overmodulation of the output voltage, in order to avoid torque ripple on the motor
shaft. This feature may be useful for applications such as grinding machines.
Function:
This is a true torque limit function that can run into the oversynchronous range above nominal motor
speed.
Motor magnetisation drop is automatically compensated by a current increase.
Function:
This is a true torque limit function that can run into the oversynchronous range above nominal motor
speed.
Motor magnetisation drop is automatically compensated by a current increase.
Function:
This is a true current limit function that continues in the oversynchronous range, however due to field
weakening the motor torque at current limit will drop accordingly when the voltage increase stops above
the synchronised speed of the motor.
Function:
Select the range of the reference signal and the feedback signal. Signal values can be positive only, or
positive and negative. The minimum limit may have a negative value, unless Speed closed loop [1] control
or Process [3] is selected in par. H-40 Configuration Mode.
Select the range of the reference signal and the feedback signal. Signal values can be positive only, or
positive and negative. The minimum limit may have a negative value, unless Speed closed loop [1] control
or Process [3] is selected in par. H-40 Configuration Mode.
For both positive and negative values (both directions, relative to par. H-08 Reverse Lock).
AF-650 GP Programming Guide