[5]
Comp cnt stop w/o r
This parameter cannot be adjusted while the motor is running.
H-84 Precise Stop Counter Value
Range:
100000*
[0 - 999999999]
3
H-85 Precise Stop Speed Compensation Delay
Range:
10 ms*
[0 - 100 ms]
H-87 Load Type
Option:
[0] *
Passive load
[1]
Active load
H-88 Minimum Inertia
Range:
0.0048
[0.0001 - par. E-69 kgm^2]
kgm^2*
This parameter cannot be adjusted while motor is running.
H-89 Maximum Inertia
Range:
0.0048
[par. E-68 - 0.4800 kgm^2]
kgm^2*
This parameter cannot be adjusted while motor is running.
3.7.8 H-9# Motor Temperature
Parameters to configure the special KTY sensor when used as a thermistor source and when Parameter F-12 Thermistor Source is enabled.
H-95 KTY Sensor Type
Option:
[0] *
KTY Sensor 1
[1]
KTY Sensor 2
[2]
KTY Sensor 3
98
Same as [3] but the number of pulses counted during ramp down to 0 rpm is deducted from the counter
value in par. H-84 Precise Stop Counter Value.
Function:
Enter the counter value to be used in the integrated precise stop function, par. H-83 Precise Stop Func-
tion.
The maximum permissible frequency at terminal 29 or 33 is 110 kHz.
Function:
Enter the delay time for sensors, PLCs, etc. for use in par. H-83 Precise Stop Function. In speed compensated
stop mode, the delay time at different frequencies has a major influence on the stop function.
Function:
For conveyers, fan and pump applications.
For hoisting applications. When Active Load [1] is selected, set par. H-66 Min. Current at Low Speed to a
level which corresponds to maximum torque.
Function:
Enter the minimum moment of inertia of the mechanical system. par. H-88 Minimum Inertia and par.
H-89 Maximum Inertia are used for pre-adjustment of the Proportional Gain in the speed control, see par.
PI-02 Speed PID Proportional Gain.
Function:
Enter the maximum moment of inertia of the mechanical system. par. H-88 Minimum Inertia and par.
H-89 Maximum Inertia are used for pre-adjustment of the Proportional Gain in the speed control, see par.
.
Function:
Select the used type of KTY sensor:
KTY Sensor type 1: 1Kohm at 100 degrees C
KTY Sensor type 2: 1Kohm at 25 degrees C
KTY Sensor type 3: 2Kohm at 25 degrees C
AF-650 GP Programming Guide