E-81 Term 32/33 Encoder Direction
Option:
[0] *
Clockwise
[1]
Counter clockwise
This parameter cannot be adjusted while the motor is running.
3.4.8 E-9# Bus Controlled
Parameters to configure digital, relay and pulse train outputs to be controlled by the serial communications.
E-90 Digital & Relay Bus Control
Range:
0*
[0 - FFFFFFFF]
Bit 0
Digital Output Terminal 27
Bit 1
Digital Output Terminal 29
Bit 2
Digital Output Terminal X 30/6
Bit 3
Digital Output Terminal X 30/7
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-15
Reserved for future terminals
Bit 16
Option C Relay 1 output terminal
Bit 17
Option C Relay 2 output terminal
Bit 18
Option C Relay 3 output terminal
Bit 19
Option C Relay 4 output terminal
Bit 20
Option C Relay 5 output terminal
Bit 21
Option C Relay 6 output terminal
Bit 22
Option C Relay 7 output terminal
Bit 23
Option C Relay 8 output terminal
Bit 24-31
Reserved for future terminals
E-93 Pulse Out #27 Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
E-94 Pulse Out #27 Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
E-95 Pulse Out #29 Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
E-96 Pulse Out #29 Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
Function:
Change the detected encoder rotation direction without changing the wiring to the encoder.
Sets channel A 90° (electrical degrees) behind channel B upon clockwise rotation of the encoder shaft.
Sets channel A 90° (electrical degrees) ahead of channel B upon clockwise rotation of the encoder shaft.
Function:
This parameter holds the state of the digital outputs and relays that is controlled by bus.
A logical '1' indicates that the output is high or active.
A logical '0' indicates that the output is low or inactive.
Function:
Set the output frequency transferred to the output terminal 27 when the terminal is configured as 'Bus
Controlled' in par. E-70 Terminal 27 Pulse Output Variable [45].
Function:
Set the output frequency transferred to the output terminal 27 when the terminal is configured as 'Bus
Ctrl Timeout' in par. E-70 Terminal 27 Pulse Output Variable [48]. And a time-out is detected.
Function:
Set the output frequency transferred to the output terminal 29 when the terminal is configured as 'Bus
Controlled' in par. E-70 Terminal 27 Pulse Output Variable [45].
Function:
Set the output frequency transferred to the output terminal 29 when the terminal is configured as 'Bus
Ctrl Timeout' in par. E-70 Terminal 27 Pulse Output Variable [48]. And a time-out is detected.