E-12 Accel Time 3
Range:
3.00 s*
[0.01 - 3600.00 s]
E-13 Decel Time 3
Range:
3.00 s*
[0.01 - 3600.00 s]
E-14 Accel Time 4
Range:
3.00 s*
[0.01 - 3600.00 s]
E-15 Decel Time 4
Range:
3.00 s*
[0.01 - 3600.00 s]
3.4.3 E-2# Digital Output
Parameters to configure terminal 27 and 29 digital outputs controlled by serial communications and to configure Relay 1 and Relay 2.
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the I/O function
for terminal 27 in par. E-51 Terminal 27 Mode, and set the I/O function for terminal 29 in par. E-52 Terminal 29 Mode. These parameters cannot be adjusted while
the motor is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready / remote control
[4]
Enable / no warning
Running
[5]
[6]
Running / no warning
[7]
Run in range / no warning
t dec s x n s RPM
Par
. E − 11 =
ref RPM
Function:
Enter the accel time from 0 RPM to the rated motor speed n
current does not exceed the current limit in par. F-43 Current Limit during ramping. The value 0.00 cor-
responds to 0.01 sec. in speed mode. See decel time in par. E-13 Decel Time 3.
Function:
Enter the decel time from the rated motor speed n
voltage arises in the inverter due to regenerative operation of the motor, and such that the generated
current does not exceed the current limit set in par. F-43 Current Limit. The value 0.00 corresponds to 0.01
s in speed mode. See accel time in par. E-12 Accel Time 3.
t dec s x n s RPM
Par
. E − 13 =
ref RPM
Function:
Enter the accel time from 0 RPM to the rated motor speed n
current does not exceed the current limit in par. F-43 Current Limit during ramping. The value 0.00 cor-
responds to 0.01 sec. in speed mode. See decel time in par. E-15 Decel Time 4.
t acc s x n s RPM
Par
. E − 14 =
ref RPM
Function:
Enter the decel time from the rated motor speed n
voltage arises in the inverter due to regenerative operation of the motor, and such that the generated
current does not exceed the current limit set in par. F-43 Current Limit. The value 0.00 corresponds to 0.01
s in speed mode. See accel time in par. E-14 Accel Time 4.
t dec s x n s RPM
Par
. E − 15 =
ref RPM
Default for all digital outputs and relay outputs
The control board receives supply voltage.
The frequency converter is ready for operation and applies a supply signal on the control board.
The frequency converter is ready for operation and is in Auto mode.
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
Motor is running.
Output speed is higher than the speed set in par. H-81 Min Speed for Function at Stop [RPM]. The motor
is running and there are no warnings.
Motor is running within the programmed current and speed ranges set in par. H-70 Warning Current
Low to par. H-73 Warning Speed High. There are no warnings.
AF-650 GP Programming Guide
. Choose a accel time such that the output
s
to 0 RPM. Choose a decel time such that no over-
s
. Choose a accel time such that the output
s
to 0 RPM. Choose a decel time such that no over-
s
3
59