Huawei NetCol8000-E220 User Manual page 181

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Alar
m ID
A279
-01
A279
-02
A279
-02
A279
-04
A279
-04
A279
-08
A27C
-01
A27C
-01
Issue 06 (2020-08-19)
Alarm
Alarm Name
Severit
y
CRITICA
Exhaust air
L
damper fault
CRITICA
Motorized
L
damper off
fault alarm
CRITICA
Exhaust air
L
damper fault
CRITICA
Motorized
L
damper
feedback fault
alarm
CRITICA
Exhaust air
L
damper fault
CRITICA
Exhaust air
L
damper fault
MAJOR
Return air 2
temp/humid
sensor fault
MAJOR
Cold aisle 1
temp/humid
sensor fault
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Probable Cause
1. The control cable
to the air damper is
loose or damaged.
2. The air damper is
faulty.
The air damper is
faulty.
The air damper is
faulty.
1. The feedback
cable to the air
damper is loose or
damaged.
2. The air damper is
faulty.
1. The feedback
cable to the air
damper is loose or
damaged.
2. The air damper is
faulty.
1. The control cable
to the air damper is
loose or damaged.
2. The air damper is
faulty.
1. The cables to the
temperature and
humidity sensor are
loose or damaged.
2. The temperature
and humidity sensor
is faulty.
1. The cables to the
temperature and
humidity sensor are
loose or damaged.
2. The temperature
and humidity sensor
is faulty.
Solution
1. Check the control
cable connection to the
air damper.
2. Maintain or replace
the air damper.
1. Maintain or replace
the air damper.
1. Maintain or replace
the air damper.
1. Check the feedback
cable connection to the
air damper.
2. Maintain or replace
the air damper.
1. Check the feedback
cable connection to the
air damper.
2. Maintain or replace
the air damper.
1. Check the control
cable connection to the
air damper.
2. Maintain or replace
the air damper.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.
1. Check the cables to
the temperature and
humidity sensor.
2. Maintain or replace
the temperature and
humidity sensor.