4.4.5 (Optional) Setting the System Power Limit Parameter

The auxiliary cooling capacity configured for the system is 50%. When the system
is used in an area where the outdoor temperature is low, the power can be
adjusted within 48–74 kW by system power limiting.
The value of System power limit is related to the overall design solution. Do not
change the value unless necessary. If System power limit is set to an incorrect
value, the upstream power supply may be abnormal.
Prerequisites
You need to log in as the admin user.
Procedure
Step 1 On the home screen, choose Settings > System Settings > System Control.
Step 2 Set Power limit function to Enable.
Figure 4-21 Setting the power limit function parameter
Step 3 Tap the text box next to System power limit.