4.3.2.8 (Optional) Setting Alarm Parameters

Prerequisites
Before setting the alarm parameters, get familiar with the relationship among each parameter.
Context
Issue 09 (2020-01-10)
Check whether the device number on the topology is the same as the actual device
number.
If yes, go to 2.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of the active devices on the topology is the same as the actual
device number.
If yes, go to 3.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of standby devices on the topology is the same as the actual
device number.
If yes, go to 4.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of online devices on the topology is the same as the actual
device number.
If yes, the check is complete.
If no, check the cable connection and the settings of teamwork control parameters.
Power underfreq alarm threshold < Power overfreq alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Return-air HT alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm threshold + 5°C ≤ Return-air HT alarm threshold
Supply-air LT alarm threshold + 5°C ≤ Return-air LT alarm threshold
Supply-air LT alarm threshold + 5°C ≤ Hot aisle LT alarm threshold
Cold aisle LT alarm threshold + 5°C ≤ Hot aisle LT alarm threshold
Cold aisle LT alarm threshold + 5°C ≤ Return-air LT alarm threshold
The content described in this section is optional. To set whether to report an alarm, or set
the time delay duration or threshold, follow the instructions in this section. The enabling
functions include the following three choices:
Allow