Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Category
Figure 3-7 Pipe support (unit: mm)
The water inlet pipe can be connected for a humidifier in two ways, as shown in the following
figure.
Issue 09 (2020-01-10)
Name
Water pressure
gauge bend
Water pressure
gauge and
thermometer
Support
Height of the U-shaped clamp (H) = Pipe diameter (with thermal insulation foam) – 5 mm.
Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away from each
bending point in turning sections.
Copyright © Huawei Technologies Co., Ltd.
Specifications
more, 20 filtration pores,
installed on the main chilled
water supply pipe
N/A
Precision level: 2.5
Operating environment:
–40° C to +70° C
Temperature influence: ≤
0.4%/10° C (operating
temperature: 20° C± 5° C)
Test pressure range: 1.2
MPa to 2.5 MPa
See
Figure
3-20.
3 Installation
Remarks
pipes reserved onsite
Engineering
procurement, based on
the system solution
Engineering
procurement, based on
the system solution
Engineering
procurement
33