Huawei NetCol5000-C Series User Manual page 29

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Item
Air supply mode
Power system
Fan type
Speed adjustment
Rated air volume
Maximum
operating pressure
Configuration of a
condensate pump
Configuration of an
air deflector
Heating function
Humidification
function
External
dimensions (H x W
x D)
Package
dimensions (H x W
x D)
Net weight
Installation mode
Certification
a refers to the test condition (return air dry/wet bulb temperature: 37.8° C/20.8° C; chilled
water inlet temperature: 10° C; water flow rate: 5.5 m
Issue 09 (2020-01-10)
NetCol5000-C030H6B2010020
E1
Horizontal flow
220 V AC, 1 Ph, 50 Hz/60 Hz
Tolerance: –10% to +10% of
rated voltage, rated frequency± 3
Hz, one active power supply, and
one standby power supply
EC fan
Stepless
3
5100 m
/h
1.6 MPa
Yes
No
No
No
2000 mm x 300 mm x 1000
mm
2000 mm x 300 mm x 1200
mm
2200 mm x 760 mm x 1350 mm
≤ 165 kg
On an ESD floor
RoHS and REACH
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-C030H6B201002
0E0
Horizontal flow
220 V AC, 1 Ph, 50 Hz/60 Hz
Tolerance: –10% to +10% of
rated voltage, rated frequency± 3
Hz, one active power supply,
and one standby power supply
EC fan
Stepless
3
5100 m
/h
1.6 MPa
No
For a 1000 mm deep model:
no
For a 1200 mm deep model:
optional
No
No
2000 mm x 300 mm x 1000
mm
2000 mm x 300 mm x 1200
mm
2200 mm x 760 mm x 1350 mm
≤ 166 kg
On an ESD floor
RoHS and REACH
3
/h).
20

Advertisement

Table of Contents
loading

Table of Contents