Huawei NetCol5000-C Series User Manual page 84

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Figure 3-50 Teamwork networking
Teamwork Networking and EMS Monitoring
If both teamwork networking and ESM monitoring are required, the smart cooling product
requires a Y-split cable for collecting and transferring information.
Y-split cable.
Figure 3-53
Figure 3-51 Y-split cable
Figure 3-52 Pin definition of a Y-split cable
Issue 09 (2020-01-10)
All smart cooling products in a teamwork group must be of the same model.
Do not directly connect the first and the last smart cooling products to form a ring
network.
The number (n) of smart cooling products in this figure should be less than or equal to 32.
The teamwork cable between two adjacent smart cooling products must not exceed 10 m in a
network.
3.14.6 Teamwork Networking and Monitoring
shows the Y-split cable connection for teamwork control.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Figure 3-51
shows a
defines the pins of a Y-split cable.
75

Advertisement

Table of Contents
loading

Table of Contents