Installation; Installation Precautions - Huawei NetCol5000-C Series User Manual

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)

3.1 Installation Precautions

To ensure the optimal operating condition and longest service life, install the NetCol5000-C
correctly as required.
Figure 3-1 Maintenance clearance 1 (unit: mm)
Issue 09 (2020-01-10)
Check whether the environment meets the requirements before installation, and whether
reconstruction is needed for routing pipes and cables and constructing ventilation pipes.
Install the NetCol5000-C according to the design drawing and reserve space for
maintenance.
Ensure that a minimum of 900 mm maintenance clearance is reserved in one of front and
back sides, and a minimum of 600 mm maintenance clearance is reserved in the other
side, as shown in the following figures.
Copyright © Huawei Technologies Co., Ltd.
3

Installation

3 Installation
25

Advertisement

Table of Contents
loading

Table of Contents