4.4.2.4 Clearing the Runtime

Context
To clear the runtime of the smart cooling product component, log in as the Admin or
Engineer user.
Performance value clearance can be performed only after component maintenance. Otherwise
the component may run overtime and degrade performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Figure 4-40 Performance maint screen
Step 2 Tap Clear of a specific performance parameter to clear its runtime.
----End

4.4.2.5 Calibrating a Sensor

Context
Procedure
Step 1 On the home screen, choose Maint > Sensor Adjust.
Issue 09 (2020-01-10)
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates from
the actual value. For example, if the return air temperature measured by other
temperature detection devices at the return air detection point is 20° C while the value
measured by the sensor is 22° C, the sensor has an error of 2° C, and the calibration value
should be set to –2° C.
To calibrate a sensor, log in as the Admin or Engineer user.
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
Figure 4-40
is displayed.
Figure 4-41
is displayed.
115