Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Figure 3-20 Support specifications (unit: mm)
(1) Bolt connecting the adapter plate and
cabinet: M10x25
(3) Bolt connecting the support and floor:
M12x60
Procedure
Step 1 The procedure for non-anchored installation on an ESD floor is as follows:
Issue 09 (2020-01-10)
It is recommended that the support be made of angle steel, square steel, or channel steel,
with a width of 58 mm and thickness of 4–5 mm.
When the width of angle steel is more than 58 mm, it generates interference with cable
holes. Cut a hole in the angle steel to avoid interference. If the width is less than or equal
to 58 mm, this operation is not required.
Install a shock absorbing bar (5 mm thick, made of EPDM rubber) at the bottom of the
support.
Control the soldering process to prevent an excessive error.
The length (L) of the support (L) is equal to the depth of the cabinet.
Copyright © Huawei Technologies Co., Ltd.
(2) Bolt connecting the adapter plate and
support: M12x25
(4) EPDM rubber shock absorbing bar
3 Installation
48