NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
3.8 Combining Cabinets
Procedure
Step 1 Combine cabinets after ensuring that they are leveled.
Figure 3-24 Combining cabinets
1.
2.
Step 2 Use the same method to secure the connecting kits at the connection positions on the rear
door.
----End
Issue 09 (2020-01-10)
Remove the cabinet connecting kits from the rack, as shown by (1) in
Secure the connecting kits at the connection positions on the front door using screws, as
shown by (2)
Figure
3-24.
Ensure that the vertical distance between each cabinet top and the floor is 2000 mm (tolerance ± 2 mm)
and that all cabinet tops are on the same plane.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Figure
3-24.
51