Optional) Setting Alarm Parameters - Huawei NetCol5000-A User Manual

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Follow-up Procedure
After you have completed the settings, check whether the teamwork networking is successful
by performing the following steps:
1.
2.
3.
4.

4.3.2.8 (Optional) Setting Alarm Parameters

Prerequisites
Before setting the alarm parameters, get familiar with the relationship among each parameter.
Configurations of temperature and humidity alarms and main board alarms for the air cooled
devices comply with the following relationships:
Configurations of temperature and humidity alarms and main board alarms for the chilled
water devices comply with the following relationships:
Issue 13 (2019-01-15)
RS485 only: Units under CAN teamwork must be free from CAN cables in between. You need to
prepare cables that support only RS485 communication. For how to make cable crimp terminals, refer to
the section of teamwork networking and monitoring.
Check whether the device number on the topology is the same as the actual device
number.
If yes, go to 2.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of the running devices on the topology is the same as the
actual device number.
If yes, go to 3.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of backup devices on the topology is the same as the actual
device number.
If yes, go to 4.
If no, check the cable connection and the settings of teamwork control parameters.
Check whether the number of online devices on the topology is the same as the actual
device number.
If yes, the check is complete.
If no, check the cable connection and the settings of teamwork control parameters.
Power underfreq alarm threshold < Power overfreq alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Return-air HT alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm threshold + 5°C ≤ Return-air HT alarm threshold
Supply-air LT alarm threshold + 5°C ≤ Return-air LT alarm threshold
Power underfreq alarm threshold < Power overfreq alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Return-air HT alarm threshold
Supply-air HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Cold aisle HT alarm threshold + 5°C ≤ Hot aisle HT alarm threshold
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
102