NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
2.
----End
3.7 Installing an Outdoor Unit
For the details about how to install the outdoor unit, see the outdoor unit user manual.
3.8 Exhausting Nitrogen
Context
Before welding refrigerant pipes, fully exhaust nitrogen from the refrigerant pipes to avoid
explosion and injuries.
Procedure
Step 1 Remove the valve bonnet of discharge pipe needle valve, as shown in
the needle valves using rubber tubes with pressure gauge.
Issue 13 (2019-01-15)
Figure 3-22 Leveling the cabinet
Use a measuring tape or right angle to check that the heights measured from the front,
rear, right, and left of the cabinet are the same.
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Figure
3-23. Connect