Table 2-5 Storage conditions
Item
Storage temperature
Storage humidity
Table 2-6 Derating coefficients
Altitude
Density
coefficient
Air volume
coefficient
Cooling
capacity
coefficient
The sensible heat ratio is all 100%.
Ports
Table 2-7
Table 2-7 Ports
Port
Refrigerant liquid pipe
Refrigerant gas pipe
Pump drainpipe
Humidifier water supply
pipe
Condensate
self-drainpipe
Issue 13 (2019-01-15)
0
1000m
m
1
0.887
1
0.887
1
0.940
describes the ports on the NetCol5000-A.
Description
Flaring copper pipe inner diameter: 5/8 inch, soldered.
Flaring copper pipe inner diameter: 7/8 inch, soldered.
Reserved: 1/2 inch BSPP (British Standard Pipe Parallel) screw
thread connector, as shown in
Reserved: 1/2 inch BSPP screw thread connector, as shown in
Figure
Reserved: 1/2 inch BSPP screw thread connector, as shown in
Figure
Copyright © Huawei Technologies Co., Ltd.
Specifications
–40° C to +70° C
5% RH to 95% RH (non-condensing)
1500m
2000m
2500m 3000m
0.835
0.785
0.737
0.835
0.785
0.737
0.909
0.878
0.846
Figure
2-7.
2-7.
2 Product Description
3500m
4000m
0.692
0.649
0.608
0.692
0.649
0.608
0.815
0.784
0.753
2-7.