Huawei NetCol5000-A User Manual page 167

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Alar
Alarm
Alarm
m
Severit
ID
y
Return-
Major
air 3
temp
invalid
a002
Return-
Critical
air HT
Return
Warnin
a003
air LT
g
a004
Return-
Major
air 3
humid
invalid
a007
Return-
Major
air 3
T/H brd
comm
failed
Issue 13 (2019-01-15)
Default
Impact
Value
N/A
The alarm
is
generated
.
45° C
The alarm
is
generated
, and the
rotational
speed of
the
compress
or
increases.
The alarm
15° C
is
generated
.
N/A
The alarm
is
generated
.
N/A
The alarm
is
generated
.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Cause
1. Dirt or water exists
around the T/H sensor,
which leads to a
detection fault.
2. The T/H sensor is
faulty.
1. The load is high or the
refrigeration capacity is
insufficient.
2. The return air temp is
higher than the
return-air HT alarm
thres during startup.
3. The ambient temp is
high.
4. The return-air HT alarm
thres is inappropriate.
5. The temp displayed is
different from the
actual temp.
1. The load is low.
2. The ambient temp is
low.
3. The return-air LT alarm
thres is inappropriate.
4. The temp displayed is
different from the
actual temp.
1. The cables to the temp
sensor are loose or
damaged.
2. The temp sensor is
faulty.
1. The cables to the T/H
sensor are loose or
damaged.
2. The DIP switch of the
T/H sensor is set
incorrectly.
3. The T/H sensor is
faulty.
4. The communication
port of the control
board is faulty.
Solution
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
1. Add more smart
cooling product units.
2. Check other causes if
the alarm persists after
startup.
3. Check the ambient
temp.
4. Adjust the return-air
HT alarm thres.
5. Calibrate or replace
the abnormal temp
sensors.
1. Please consult Huawei
technical support.
2. Check the ambient
temp.
3. Adjust the return-air
LT alarm thres.
4. Calibrate or replace
the abnormal temp
sensors.
1. Check the cables to the
temp sensor.
2. Maintain or replace the
temp sensor.
1. Check the cables to the
T/H sensor.
2. Set the DIP switch of
the T/H sensor
correctly.
3. Maintain or replace the
T/H sensor.
4. Maintain or replace the
control board.
158