When you route pipes from the top, remove the two upper plugs, connect discharge pipe to
the air outlet pipe of the outdoor unit, and connect liquid pipe to the liquid inlet pipe of the
outdoor unit, as shown in
Figure 3-28 Routing pipes from the top
(1) Gas pipe

3.9.2 Connecting Water Pipes

Context
The pipes to be connected are the humidifier water inlet pipe, condensate pump drainpipe, and
self-drainpipe. Determine the pipe to be connected based on condensate pumps, heaters, and
humidifiers, as described in
Table 3-14 Overview
Configuration
Condensate pump,
heater, and humidifier
Issue 13 (2019-01-15)
Figure
3-28.
Table
3-14.
Pipes to Be Connected
Humidifier water inlet pipe, condensate pump drainpipe, and
self-drainpipe (optional)
NOTE
Optional: If there are raised floors or bases, connect the self-drainpipe.
Otherwise, you are not required to connect the self-drainpipe. Condensate
pump drainpipe and self-drainpipe should not be connected together to
avoid water in the self-drainpipe flowing back to the pump.