NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Figure 3-21 Securing the cabinet
----End
3.6.2 Installing an Indoor Unit in Non-securing Mode
Prerequisites
Non-securing mode applies to scenarios where the indoor unit is to be installed on a floor
while no base is available.
Procedure
Step 1 Place the cabinet.
1.
2.
Step 2 Level the cabinet.
1.
Issue 13 (2019-01-15)
Determine the installation position according to the plan.
Move the cabinet to the installation position.
Raise the cabinet by adjusting the leveling feet using a wrench, as shown in
Ensure that the leveling feet contact the floor and the castors hang in the air.
Spin the castors. If the castors rotate freely, they are hanging in the air.
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Figure
3-22.
46