Refrigerant Oil; Pipe Components - Huawei NetCol5000-A User Manual

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Temperature
(° C)
18

3.1.2.2 Refrigerant Oil

The recommended refrigerant oil is Danfoss 160SZ. You can purchase it from Huawei, or
purchase it by yourself after being confirmed by Huawei.

3.1.2.3 Pipe Components

Pipe components are optional and include:
Figure 3-2 Oil trap and inverted traps (unit: mm)
Issue 13 (2019-01-15)
Saturation
Pressure-S
urface
Pressure
(MPa)
1.27
If the low-temperature component is connected, additional refrigerant oil. If not, ignore the refrigerant
oil.
Liquid pipe: copper pipe (for R410A) external diameter: 5/8 inch; thickness: 1.0 mm;
pressure tolerance range: ≥ 4.5 MPa.
Gas pipe: copper pipe (for R410A) external diameter: 7/8 inch; thickness: 1.2 mm;
pressure tolerance range: ≥ 4.5 MPa.
Thermal insulation foam: thickness ≥ 13 mm.
Oil traps and inverted traps: To ensure the NetCol5000-A reliability, make an oil trap
every 5 m to 6 m along pipes in the vertical direction and make an inverted trap
respectively at the intake vent and exhaust vent of the outdoor unit.
specifications for the oil traps and inverted traps.
Copyright © Huawei Technologies Co., Ltd.
Temperature
Saturation
(° C)
Pressure-S
urface
Pressure
(MPa)
37
2.15
3 Installation Guide
Temperatur
Saturati
e (° C)
on
Pressure
-Surface
Pressure
(MPa)
N/A
N/A
Figure 3-2
shows the
27