Huawei NetCol5000-A User Manual page 60

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Table 3-13 Recommended pipe specifications
Pipe Length (m)
L ≤ 60
Note: If the pipe is longer than 60 m, contact Huawei technical support.
Procedure
Step 1 Remove the two plugs from the pipes using a welding torch, as shown in
Figure 3-25 Routing pipes from the bottom
Step 2 Take two 90° bent copper pipes among the fittings.
Step 3 Weld the two pipes with the bent ends facing downwards, as shown in
Issue 13 (2019-01-15)
Recommended Diameter
for Discharge Pipes (inch)
7/8
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Recommended Diameter
for Liquid Pipes (inch)
5/8
Figure
3-25.
Figure
3-26.
51