Huawei NetCol5000-A User Manual page 80

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Teamwork Networking
If only teamwork communication is required, reserve the teamwork communication port 1 of
the first unit, connect the teamwork communication port 2 of the unit to the teamwork
communication port 1 of the second unit, and connect the teamwork communication port 2 of
the second unit to the teamwork communication port 1 of the third unit. All units that require
teamwork can be connected in this way, as shown in
Figure 3-46 Teamwork networking
Teamwork Networking and EMS Monitoring
If both teamwork networking and ESM monitoring are required, the smart cooling product
requires a Y-split cable for collecting and transferring information.
Y-split cable.
cable connection for teamwork control.
Figure 3-47 Y-split cable
Issue 13 (2019-01-15)
All smart cooling products in a teamwork group must be of the same model.
Do not directly connect the first and the last smart cooling products to form a ring
network.
The number (n) of smart cooling products in this figure should be less than or equal to 32.
The teamwork cable between two adjacent smart cooling products must not exceed 10 m in a
network.
Figure 3-48
defines the pins of a Y-split cable.
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Figure
3-46.
Figure 3-47
Figure 3-49
shows the Y-split
shows a
71