Huawei NetCol5000-A User Manual page 136

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
----End
4.5.10 Which Parameters Are Restored to Default Values After
Default Settings Are Operated
After choosing Settings > Restore Defaults > Yes, the following parameters are displayed:
To prevent loss of important data, record all parameter values before restoring default settings.
After restoring default settings, change the parameter values to the recorded values.
4.5.11 How to Change the SSH Access Password
Context
Procedure
Step 1 Log in to the controller over SSH.
Issue 13 (2019-01-15)
Required humidity: indicates the total dehumidification and humidification requirements of the
group and is used as a reference for enabling the dehumidification and humidification mode by the
master device.
All parameters displayed on Settings > System Settings.
All parameters displayed on Settings > Alarm Settings.
All parameters displayed on Settings > Comm Settings.
Date format and time zone settings displayed on Settings > User Settings.
All parameters displayed on Maint > Sensor Adjust.
After default settings are restored, all communication addresses are changed to 1 and the communication
between all devices and the EMS is disconnected. The communication addresses must be reset to
recover the communication.
SSH is used only for advanced maintenance.
Change the preset password in your first login to the controller over SSH.
Except for password changes, do not perform any other operations. Otherwise, the
controller cannot work properly.
Except for password changes, operations resulting in controller faults are beyond the
warranty scope.
Remember the new password.
When Windows accesses the controller over SSH, you need to use client software such as PuTTY.
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025Netcol5000-a-035

Table of Contents