Initial Configuration; Setting Temperature And Humidity Values And Enabling T/H Sensors - Huawei NetCol8000-E220 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
No.
12

4.4 Initial Configuration

● When configuring the temperature and humidity parameters, do not place the
cursor between the decimal point and the following digit of the value.
Otherwise, the decimal point cannot be deleted, and the parameter value fails
to be configured.
● When no air damper is configured, do not enable the air damper function.
Otherwise, the air damper communication failure alarm will be generated,
causing the device to work abnormally.
4.4.1 Setting Temperature and Humidity Values and Enabling
T/H Sensors
Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
is displayed.
Issue 06 (2020-08-19)
Items
Teamwork control
button
NO TICE
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
If you need to enable a humidity and temperature sensor, log in as the admin
user.
This section describes how to enable Cold aisle sensor 1.
Copyright © Huawei Technologies Co., Ltd.
Note
indicates that there is no teamwork
control at present.
teamwork control without alarms at present.
indicates that there is teamwork control
with alarms at present.
Step
2.
4 Power-on and Commissioning
indicates that there is
Figure 4-4
86