6.4 Initial Configuration

● When configuring the temperature and humidity parameters, do not place the
cursor between the decimal point and the following digit of the value.
Otherwise, the decimal point cannot be deleted, and the parameter value fails
to be configured.
● When no air damper is configured, do not enable the air damper function.
Otherwise, the air damper communication failure alarm will be generated,
causing the device to work abnormally.

6.4.1 Setting T/H Sensor Parameters

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Figure 6-3 T/H Sensor
Issue 04 (2022-06-30)
Item
Teamwork control
button
NO TICE
The T/H sensors outside the unit need to be enabled when they are installed;
otherwise, retain the default settings.
This section describes how to enable Cold aisle sensor 1.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Note
indicates that teamwork control is
disabled.
indicates that teamwork control is
enabled and no teamwork control alarm is
generated.
indicates that teamwork control is
enabled and a teamwork control alarm is
generated.
82