FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
3.1 Technical Specifications
Table 3-1 System specifications
Item
Total cooling capacity
Sensible heat
Sensible heat ratio
System dimensions (H x W x D)
Power specifications
Air filter level on the air supply side
of equipment room (EN779)
Air filter level on the outdoor air
intake side (EN779)
Number of fans
Fan type
Outdoor cold air volume
Humidification capacity (kg/h)
Heat exchanger core type
Net weight (kg)
Running weight (kg)
Issue 04 (2022-06-30)
3
Copyright © Huawei Technologies Co., Ltd.
Product Specifications
Specifications
1
400 kW
1
400 kW
100%
3600 mm x 3500 mm x 6058 mm
380–415 V AC, 3 PH, 50/60 Hz
G4
G3
● Exhaust fan: 8
● Indoor fan: 8
EC
3
100,000 m
/h
18
Plate
10000
11000
3 Product Specifications