Parameter
Auxiliary cooling
power limit
Balance of water and
electricity
consumption
Wet mode startup
temperature
Dehumidifying
function
DO_1 action
DO_2 action
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Description
● Enable: The power for auxiliary
cooling cannot exceed this value in
any case.
● Disable: The power for auxiliary
cooling is not limited in any case.
This parameter can be set to Power
saving mode, Normal water saving
mode, Extreme water saving mode,
Customized mode, or Disable water
mode. Set this parameter based on the
site requirements.
NOTE
You are advised to retain the default value.
This parameter is displayed when
Balance of water and electricity
consumption is set to Customized
mode.
Set this parameter as required.
● Enable: The device starts
dehumidifying when the ambient
humidity is higher than the
humidity setpoint.
● Disable: The dehumidifying function
is disabled.
This parameter can be set to On or
Off, and is used together with DO_1.
For details, see DO_1 description.
This parameter can be set to On or
Off, and is used together with DO_2.
For details, see DO_2 description.