Verifying The Installation - Huawei FusionCol8000-E400 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Table 5-1 System checklist
Check
Item
Unit
Fan
Water
system
Compres
sor
Differen
tial
Issue 04 (2022-06-30)
5

Verifying the Installation

Expected Result
The unit is installed properly without any tilt.
Sundries (such as desiccant, cable ties, cable
ends, dust, iron scraps, copper wires, and
aluminum scraps) inside the cabinet have been
removed.
The fan is secured.
There are no sundries inside the fan.
The fan blades rotate properly.
The water pump is secured.
The water filter is secured.
The liquid level sensor runs smoothly.
Pipes are connected securely without leakage.
The water tank is free of foreign matter, and
the filter and drainage port are not blocked.
The drip pan is free of foreign matter inside
and its drainage port is unblocked.
The sheet metal fasteners on the compressor
have been removed.
The bolts for securing the compressor are
tightened.
The pressure inlet tube is secured using cable
ties and not deformed.
Copyright © Huawei Technologies Co., Ltd.
5 Verifying the Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed