Huawei FusionCol8000-E400 User Manual page 82

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Tab
System
Optional
Parts
Issue 04 (2022-06-30)
Parameter
Teamwork function
Number of systems in
this group
Number of running
systems in this group
Teamwork power limit
function
Supply air sensor
Cold aisle sensor
Hot aisle sensor
Outdoor intake air
sensor 3
Cold aisle
temperature and
humidity sharing
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Description
Specifies whether to enable the
teamwork function. Set this parameter
based on onsite heat load distribution.
● Disable: A unit operates
independently.
● Enable: A unit operates in team
with other units.
Specifies the total number of units in
this group. The value is an integer
ranging from 1 to 32.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Specifies the number of running units
in this group. The value is an integer
ranging from 1 to the value of
Number of systems in this group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Limits the power of the teamwork
group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
This function can be enabled only
when at least one smart cooling
product in the teamwork group is
equipped with cold aisle T/H sensors. If
this function is enabled, the master
unit in the teamwork group collects
the cold aisle temperature and
humidity values from all units
equipped with cold aisle sensors, and
synchronizes the temperature and
humidity control type and setpoints to
all slave units.
74

Advertisement

Table of Contents
loading

Table of Contents