Huawei FusionCol8000-E400 User Manual page 110

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E400:
Table of Contents

Advertisement

FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
Check Item
All doors are closed.
The return air damper/return air fire damper and supply
air damper/supply air fire damper are closed.
CAUTION
If they are not closed, condensation, frost, and freezing may occur
on the indoor circulation side of the unit.
Issue 04 (2022-06-30)
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Actual Result
□ Passed □ Failed
□ Passed □ Failed
102