Step 5 After power-on, the compressor starts preheating, and the system generates an
alarm indicating that the compressor is preheating. Do not start the smart cooling
product before the preheating is complete. Choose Running > Device Details >
Compressor to view the remaining preheating time of the compressor.
----End

6.3 Home Screen

The home screen of the display module displays the system status and allows you
to access other function menus, such as Running, Alarms and Settings.
The information in the screenshots is for reference only. The actual parameters
prevail.
Figure 6-2 Home screen
Issue 04 (2022-06-30)
Parameter
Modbus Comm
address
If the return air temperature is greater than 10°C upon power-on, the
preheating time is 6 hours.
If the return air temperature is less than or equal to 10°C or invalid upon
power-on, the preheating time is 12 hours.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Description
Enter the communication address
planned for the smart cooling product.
The management system
communicates with the smart cooling
product through this address. The
communication addresses of the two
smart cooling products connected to
the same management system must
be different.