NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
Comm
Settings
----End
5.3 Home Screen
The home screen of the display module displays the system status and allows you
to access other function menus, such as Running, Alarms, and Settings.
5-2
User interfaces displayed in this document are for reference only.
Issue 06 (2022-12-15)
Parameter
Temperature
setpoint
Humidity setpoint
Modbus comm
address
shows the home screen of the display module.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
Description
After the temperature and humidity control
type and the temperature value under this
type are set, the device performs regulation
based on the settings.
● Return air: The value ranges from 18°C
to 45°C.
● Supply air: The value ranges from 15°C
to 35°C.
● Cold aisle: The value ranges from 15°C to
35°C.
● Hot aisle: The value ranges from 18°C to
45°C.
After the temperature and humidity control
type and the humidity value under this type
are set, the device performs regulation
based on the settings.
40%–60% is recommended.
Enter the communication address planned
for the smart cooling product. The
management system communicates with
the smart cooling product through this
address. The communication addresses of
the two smart cooling products connected
to the same management system must be
different.
Figure
100