Step 1 Clean the engineering pipe and remove the thermal insulation foam from the
drainpipe plug.
Step 2 Remove the drainpipe plug.
Step 3 Install a pipe adapter and seal it with sealant.
Step 4 (Rigid pipe connection) Connect the water pipe using a hot melt device and
connect the drainpipe to the external drainage system.
(Hose connection) Secure the hose using hose clamps and connect the drainpipe
to the external drainage system.
Step 5 Wrap thermal insulation foam around the pipe.
Figure 4-43 Connecting the automatic drainpipe (rigid pipe connection)
Figure 4-44 Connecting the forcible drainpipe (rigid pipe connection)
Figure 4-45 Connecting the drainpipe (hose connection)
----End

4.10.3 (Optional) Connecting the Humidifier Water Inlet Pipe

Context
Procedure
Step 1 Install an adapter for the humidifier inlet water pipe. A sealing washer is
recommended.
Issue 06 (2022-12-15)
A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
The product is permanently connected to the water source and cannot be
connected using a hose assembly.