Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Parameter
Humidity
setpoint
The relationship between the temperature setpoint and the humidity setpoint is as
follows: Under the condition that the absolute humidity range is [0.0026, 0.0141]
for the default temperature setpoint 23°C and relative humidity range [15% RH,
80% RH], ensure that the absolute humidity range is [0.0026, 0.0141] when you
set the temperature setpoint and humidity setpoint.
Table 5-5 Setting example
Temperature Setpoint
(°C)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Issue 06 (2022-12-15)
Description
After the temperature and
humidity control type and the
humidity value under this type
are set, the device performs
humidifying or dehumidifying
based on the settings.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Lower Limit of
Humidity Setpoint (%
RH)
24.7
23.1
21.7
20.4
19.2
18
16.9
15.9
15
15
15
15
15
15
15
15
15
15
5 Power-On Commissioning
Configuration Principle
Set this parameter as required.
40%–60% RH recommended
Upper Limit of
Humidity Setpoint (%
RH)
80
80
80
80
80
80
80
80
80
75.3
70.9
66.9
63
59.5
56.1
53
50
47.3
105