Figure 4-35 Leveling a cabinet
● Wrench an anchor bolt clockwise to elevate a cabinet, wrench an anchor bolt
anticlockwise to lower a cabinet. The leveling feet can be adjusted within a
range of 0–8 mm.
● To prevent damaged caused by cabinet tilt, adjust all the leveling feet at the
four corners instead of one foot.
● Use a measuring tape to check that the vertical distance between the top of
the cabinet and the floor is 2000 mm±2 mm or 2200 mm±2 mm.
● Do not remove the leveling feet. Otherwise, you need to rework them for use.
Step 2 Combine cabinets, as shown in the following figure.
Figure 4-36 Combining cabinets
1.
Issue 06 (2022-12-15)
NO TICE
Remove the connecting kits from the cabinets.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
65