Leveling And Combining Cabinets (Netcol5000-C030/C032) - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 4-34 Combining cabinets (rear door)
1.
2.
Step 3 Secure the connecting kits at the connection positions on the rear door using
screws in the same way.
----End
4.8.2 Leveling and Combining Cabinets (NetCol5000-C030/
C032)
Procedure
Step 1 Level the cabinet. Use a socket wrench to adjust the leveling feet at the bottom of
the smart cooling product, and use a measuring tape and a level to adjust the
horizontal and vertical distances of the smart cooling product. Ensure that the
leveling feet touch the floor after adjustment, as shown in
Issue 06 (2022-12-15)
Remove the connecting kits from the cabinets.
Secure the connecting kits at the connection positions on the front door using
screws.
NO TE
Ensure that the vertical distance between each device top and the floor is 2000 mm (±2
mm) and that all device tops are on the same plane.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
Figure
4-35.
64