5.5.2 (Optional) Setting the Pressure Difference Control

Prerequisites
If micro differential pressure sensors are installed, perform the following
operations accordingly. If micro differential pressure sensors are not installed, skip
this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0–50 Pa.
Step 2 Set Indoor fan control type to Pressure diff ctrl.
Step 3 Change the other parameters based on the following instructions.
Issue 06 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Lower Limit of
Humidity Setpoint (%
RH)
15
15
15
15
15
15
15
15
15
15
15
15
15
5 Power-On Commissioning
Upper Limit of
Humidity Setpoint (%
RH)
44.7
42.2
40
37.8
35.8
33.9
32.1
30.5
28.9
27.4
26
24.7
23.4
106