FusionCol8000-E400 Modular Indirect Evaporative
Cooling System
User Manual
----End
6.7 (Optional) Power-Off
Context
In shutdown mode, the Shutdown button is green (unavailable) and the Start
button is gray (available).
Procedure
Step 1 Tap Shutdown on the home screen of the display module. A warning is displayed,
indicating whether to shut down the unit.
Step 2 Tap Confirm. If the device is successfully shut down, the system displays a
message, indicating that the command is successfully triggered.
Step 3 Turn off the unit switch in the PDF.
----End
6.8 Checking After Commissioning
Table 6-3 Commissioning checklist
Check Item
No oil stain exists on the copper pipe thermal insulation
foam or bottom plate, or it has been cleaned.
The needle valve plug is secured (torque of 0.45±0.05
N·m), and the valve bonnet is tightened.
The foreign matter inside the water pan and bottom plate
is cleaned up.
The air filter is correctly installed according to the airflow
direction marked on the frame.
The condensate water is drained smoothly from the water
pan in the maintenance door.
Issue 04 (2022-06-30)
Figure 6-19 Wizard-based startup result
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
Actual Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
101