An inverter can join the link system as a CC-Link remote device station, and such device stations can be controlled and
monitored with a user program of a programmable controller. These devices can be useful components of an automated
factory.
Connect shielding wires of the CC-Link dedicated cable to "SLD" of each unit.
Terminating
resistor
*1
Use the terminating resistors supplied with the programmable controller.
*2
Set "1" and "2" of the terminating resistor selection switch to OFF (without terminating resistor) in the middle units. (Refer to
*3
Set the terminating resistor selection switch. (Refer to
Do not use the built-in terminating resistor selection switch when using a one-touch connecter plug with terminating resistor. (1-OFF, 2-
OFF) (Refer to
Maximum number of units connected to one master station (CC-Link Ver.1.10)
42 units (when connections are inverters only)
If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must
be satisfied:
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64
a: Number of units occupying 1 station c: Number of units occupying 3 stations
b: Number of units occupying 2 stations d: Number of units occupying 4 stations
{(16 × A) + (54 × B) + (88 × C)} ≤ 2304
A: Number of remote I/O ≤ 64
B: Number of remote device stations ≤ 42
C: Number of local, standby master and intelligent device stations ≤ 26
30
WIRING
Master module
Blue
DA
White
DB
∗1
Yellow
DG
SLD
Shielded
twisted cable
page 27
for the details of the one-touch connector plug with terminating resistor.)
FR-A8NC
FR-A8NC
∗2
Blue
DA
White
DB
Yellow
DG
SLD
Shielded
twisted cable
page
20.)
DA
Terminating resistor
DB
selection switch
∗3
DG
SLD
page
20.)